AFS-(WM/DM) F200 Integration
FMS Configuration
Figure 8.1: FMS Wiring
1 2 3
SW1
SW2
SW3
FMS AFS-xx Input Configuration Interface
1
2
3
4
P1
VDC
TB1
VDC
+ -
EXTERNAL
24VDC
+ +
Ch1
+ -
Ch2
+ -
Ch3
+ -
Ch4
+ -
TB2 Input 1-4
Ch5
+ -
Ch6
+ -
Ch7
+ -
TB3 Input 5-8
Ch8
+ -
EXTERNAL
GND
- -
TB4
NC NO C
RELAY 1
NC NO C
RELAY 2
1. Set Jumper Switches on AFS-XX to appropriate
settings.
Output Selection SW1: 4-20mA Output
Working Range SW2: 0-2000 Ft/Min Range
0-3000 Ft/Min Range
0-4000 Ft/Min Range
Response Time SW3: Fast
Slow
2. Set FMS Input Channel to an Analog 4-20 mA.
3. For a 0-2000 Ft/Min Range, use a gain of 500 and an
offset of -500.
4. For other settings, use the integrated gain/offset
calculator.